Maximal33R rack mount access power controller distributes and switches power
to access control systems and accessories. It converts a 115VAC 50/60Hz input
into sixteen (16) independently controlled 12VDC and/or 24VDC fuse pro-
tected outputs. Outputs are activated by an normally open (NO) or normally
closed (NC) dry trigger input from an Access Control System, Card Reader,
Keypad, Push Button, PIR, etc. This unit will route power to a variety of access
control hardware devices including: Mag Locks, Electric Strikes, Magnetic
Door Holders, etc.
Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP
Interface enables Emergency Egress, Alarm Monitoring, or may be used to
trigger other auxiliary devices. The fire alarm disconnect feature is individually
selectable for any or all of the outputs.
Input:
• 115VAC60Hz.,3.8amp.
• Normallyclosed[NC]ornormallyopen[NO]
dry contact inputs (switch selectable).
Outputs:
• 12VDCor24VDC@12amptotaloutputcurrent.
Powersupply1/(8)outputs:
12VDC@6ampor24VDC@6amp
Powersupply2/(8)outputs:
12VDC@6ampor24VDC@6amp
• Sixteen(16)fuseprotectedoutputs.
• MaximumcurrentperACM8R-Moutputis2.5amp.
• IndividuallyselectableMagLock/Strike(Fail-Safe,
Fail-Secure) solid state fuse protected outputs.
• Thermalandshortcircuitprotectionwithautoreset.
Fire Alarm Interface:
• LatchingorNon-Latchingfirealarmresetswitch
individually selectable for each output.
• RemoteresetcapabilityforlatchingFireAlarm
Interface mode.
• FireAlarmdisconnectinputoptions:
a)Normallyopen[NO]ornormallyclosed[NC]
dry contact input.
b)Polarity reversal input from FACP signaling
circuit.
Visual Indicators:
• IndividualOutputStatusLEDslocatedonthe
front panel.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltype
batteries (if batteries are required install
separate enclosure).
• Maximumchargecurrent0.7amp.
• Automaticswitchovertostand-bybattery
when AC fails.
• Zerovoltagedropwhenunitswitchesovertobattery
backup (AC failure condition).
Supervision:
• ACfailsupervision(form“C”contact).
• Lowbatteryandbatterypresencesupervision
(form“C”contact).
Additional Features:
• Removableterminalblockswithlockingscrewflange.
• 3-wirelinecord.
• Illuminatedmasterpowerdisconnectcircuitbreaker
with manual reset.
Mechanical:
• Dimensions(HxWxD)(approx.):3.25”(82.55mm)x
19.125”(485.78mm)x8.5”(215.9mm)
• Shipping Weight (approximate): 14.3 lbs (6.49kg).
Maximal33R
Rack Mount Access Power Controller
Rev. DSMaximal33R - 11012012
Overview
Specifications
Maximal33R
Vue de la page 0
1 2

Résumé du contenu

Page 1 - Maximal33R

Maximal33R rack mount access power controller distributes and switches power to access control systems and accessories. It converts a 115VAC 50/60Hz

Page 2 - TOP & BOTTOM

Altronix Corp. - 140 58th Street, Brooklyn, NY 11220 • 718-567-8181 • 888-258-7669 • altronix.comFRONTTOP & BOTTOMREARMaximal33R Rack Chassis Dime

Commentaires sur ces manuels

Pas de commentaire