Input:
• Powerinput:120VAC60Hz,4.8amp.
• Two(2)ClassAortwo(2)ClassBFACPinputs.
• Two(2)configurableinputstriggerviaClassAor
ClassBFACPsignalcircuits(polarityreversal)or
drycontacts.
Output:
• 24VDCvoltageregulatedpower-limitedNACoutputs.
• Outputpower:
10ampmax.totalalarmcurrent.
7ampmax.stand-bywithoutbatteryback-up.
1ampwithbatteryback-upincluding
dedicatedAux.output.
For Canadian applications Stand-by with
battery backup is limited to 0.45 amp.
• 2.5ampmaxcurrentperoutput.
• One(1)auxiliaryoutputratedat1amp
(regulated,batterybackedup).
0.45 amp for Canadian applications.
• AnyNACcanbeconfiguredasanAux.outputwithor
withoutbatteryback-up(specialapplicationonly).
WhensetasAux.output,theoutputisnotsupervised.
• Programmablesupervisedindicatingcircuitoutputs:
Eight(8)ClassBorFour(4)ClassA,
oranycombinationofClassAandClassBcircuits.
• Thermalandshortcircuitprotectionwithautoreset.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Automaticswitchovertostand-bybatterywhen
ACfails.
• Zerovoltagedropwhenswitchingoverto
batterybackup.
Supervision:
• ACfailsupervision(form“C”contacts).
• Batteryfail&presencesupervision(form“C”contacts).
• Lowpowershutdown.ShutsdownDCoutputterminals
ifbatteryvoltagedropsbelow70-75%for24Vunits.
Preventsdeepbatterydischarge.
Special Features:
• ProgrammableLCDdisplayinterface.
• Ethernetportinterfaceforremoteprogrammability
andmonitoring.
• 2-wirehorn/strobeSyncmodeallowsaudible
notificationappliances(horns)tobesilenced
whilevisualnotificationappliances(strobes)
continuetooperate.
• TemporalCode3,SteadyMode,InputtoOutput
FollowerMode(maintainssynchronizationof
notificationappliancescircuit).
• Compatiblewith12VDCor24VDCfirepanels.
• Outputloopsupervisiondirectedtoinput1orinput2.
• CommontroubleDryN.C.outputforreporting
troubletoremoteFACP.
• Groundfaultdetection-Groundfaultmaximumtest
impedance1,000ohm.
• GroundfaultDryN.O.outputtoreportgroundfault
toremoteFACP.
Electrical:
• Operatingtemperature:0ºCto49ºCambient.
• BTU/Hr.:122.84BTU/Hr.
• SystemACinputVArequirement:576VA.
Visual Indicators:
• LCDdisplay-Indicatestroublesandconditionsof
operation.TroubleConditionMemoryfacilitates
quickidentificationofanintermittent/fault
(shortcircuit,openorground)whichhaspreviously
occurredononeormoresignalingcircuitoutputs.
LCDdisplayswhichoutputthefaulthasoccurredon.
Mechanical:
• EnclosureDimensions(HxWxDapprox.):
15.5”(393.7mm)x12”(304.8mm)x4.5”(114.3mm)
- Accommodatesuptotwo(2)12VDC/12AHbatteries.
• Productweight(approx.):12.4lbs.(5.62kg).
• Shippingweight(approx.):13.7lbs.(6.21kg).
Specifications
TheAltronixFireSwitch108isacosteffectivemanagedNACPowerExtender.Itinterfaces
with 12 or 24VDC Fire Alarm Control Panels (FACP) to provide Notification Appliance
Circuitexpansionsupport,foradditionalhorns/strobestoallowADAcompliancy.Italsopro-
videsauxiliarypowertosupportsystemaccessories.Itdeliverselectronicallyregulatedand
filtered24VDCpowertoClassBorClassANACloopcircuits.Additionally,aseparate1amp
auxiliaryoutputfor4-wiresmokedetectorsisavailable.Alarmcurrentcanbedividedbetween
theeight(8)outputsforpoweringNACdevices.Outputsareratedat2.5ampmax.,andcan
beindependentlyprogrammedforSteady,TemporalCode3orStrobeSynchronization.All
outputsmaybeprogrammedforInputtoOutputFollowerMode
(outputwillfollowinput.i.e.MarchTimeInput,MarchTime
Output).Innon-alarmconditionindependentloopsupervision
forClassAand/orClassBFACPNACcircuitsisprovided.Intheeventofalooptrouble,theFACPwillbenotified
viathesteeredinput(input1orinput2).Inaddition,therearecommontroubleoutputterminals[NC,C,NO]which
areusedtoindicategeneralloop/systemtrouble.Two(2)FACPsignalingoutputscanbeemployedanddirectedto
controlsupervisionandpowerdeliverytoanycombinationoftheeight(8)outputs.ItprovidesaprogrammableLCD
displayinterface,plusanethernetportinterfaceforremoteprogrammabilityandmonitoring.
FireSwitch108
Managed NAC Power Extender
Rev.DSFireSwitch108_02082013
FireSwitch108
Overview
Vue de la page 0
1 2

Résumé du contenu

Page 1 - Managed NAC Power Extender

Input:• Powerinput:120VAC60Hz,4.8amp.• Two(2)ClassAortwo(2)ClassBFACPinputs.• Two(2)configurableinputstriggerviaClassAor Cl

Page 2 - Agency Approvals

Altronix Corp. - 140 58th Street, Brooklyn, NY 11220 • 718-567-8181 • 888-258-7669 • altronix.comEnclosure Dimensions (H x W x D) (approximate):15.5”

Commentaires sur ces manuels

Pas de commentaire