SMP1012Xseries - 1 -
Overview:
These units will convert a 115VAC 50/60Hz input into a regulated 12VDC output at up to 10 amp continuous supply
current (see specifications).
SMP1012X Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Accessory
Power
Distribution
Module(s)
Number of
Outputs
Fused Outputs
PTC Outputs
Output Rating
(amp) per Output
Supervised
115VAC
50/60Hz Input
Current (amp)
12VDC Total
Output Current
(amp)
SMP10C12X
- 1 - - 10 - 1.45 10
SMP10C12XX*
- 1 - - 10 - 1.45 10
SMP10PMC12X
- 1 - - 10 x 1.45 10
SMP10PMC12XX*
- 1 - - 10 x 1.45 10
SMP10PM12P4
PD4 4 - 3.5 x 1.45 10
SMP10PM12P4CB
PD4CB 4 - x 2.5 x 1.45 10
SMP10PM12P8
PD8 8 x - 3.5 x 1.45 10
SMP10PM12P8CB
PD8CB 8 - x 2.5 x 1.45 10
SMP10PM12P16
PD16W 16 x - 3.5 x 1.45 10
SMP10PM12P16CB
PD16WCB 16 - x 2.5 x 1.45 10
*Refer to Enclosure Dimensions on pg.7 for enclosure size.
Specifications:
Installation Instructions:
Wiring methods should be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install three fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 6-7).
Secure enclosure to earth ground.
2. Connect AC power to the terminals marked [L & N].
Use 18 AWG or larger for all power connections (Battery, DC output).
3. Measure output voltage before connecting devices. This helps avoiding potential damage.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Maximumchargecurrent0.7amp.
• Filteredandelectronicallyregulatedoutputs.
• Automaticswitchovertostand-bybatterywhen
AC fails (zero voltage drop).
Features:
• ACinputandDCoutputLEDindicators.
Features (cont’d):
• Shortcircuitandthermaloverloadprotection.
• Completewithpowersupply,powerdistributionmodule
(when applicable), enclosure, cam lock & battery leads.
• PowerON/OFFswitch.
Supervised models only:
• ACfailsupervision(form“C”contacts).
• Lowbatterysupervision(form“C”contacts).
SMP1012X Series - Installation Guide
Vue de la page 0
1 2 3 4 5 6 7 8

Résumé du contenu

Page 1 - SMP1012Xseries - 1

SMP1012Xseries - 1 - Overview:These units will convert a 115VAC 50/60Hz input into a regulated 12VDC output at up to 10 amp continuous supply curre

Page 2 - Power Supply

- 2 - SMP1012Xseries4. Connect devices to be powered: a. For Power Supply Board connect to the terminals marked [– DC +]. b. For Power Distribu

Page 3

SMP1012Xseries - 3 - Earth GroundWire Strap(fromEnclosureto Door)115 power mainsCAUTION: De-energize unit prior to servicing. For continued protect

Page 4 - Installed)

- 4 - SMP1012XseriesINPUTLEDPD4POWER DISTRIBUTING UNIT1P, 2P, 3P, 4P = FUSED OUTPUTS1N, 2N, 3N, 4N = COMMON OUTPUTSF1F1F2 F3 F4COMMON POWER OU

Page 5 - Power Supply Board

SMP1012Xseries - 5 - Terminal Identification:Power Supply BoardTerminal Legend Function/Description L, G, N Connect 115VAC to these terminals: L t

Page 6 - SMP10C12X SMP10PMC12X

- 6 - SMP1012XseriesEnclosure Dimensions for:SMP10C12X SMP10PMC12XSMP10PM12P4 SMP10PM12P4CBSMP10PM12P8 SMP10PM12P8CBSMP10PM12P16 SMP10PM12P1

Page 7 - SMP10PMC12XX

SMP1012Xseries - 7 - Enclosure Dimensions for:SMP10C12XXSMP10PMC12XX15.5”x12”x4.5”(393.7mmx304.8mmx114.3mm)1.5”(38.1mm)1.5”(38.1mm)1.5”(38

Page 8 - - 8 - SMP1012Xseries

- 8 - SMP1012XseriesAltronix is not responsible for any typographical errors. Product specifications are subject to change without notice.14058th

Commentaires sur ces manuels