Overview:
This power supply/charger converts 115VAC / 60Hz or 220VAC / 50Hz input, into a 24VDC @ 12 amp of continuous
supply current (see specifications).
Specifications:
Installation Instructions:
Unit should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount the unit in desired location/enclosure.
2. Connect AC power to terminals marked [L & N], connect ground to terminal marked [G].
Use 18 AWG or larger for all power connections (Battery, DC output, AC input).
Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).
3. Connect devices to be powered to terminals marked [--- DC +].
Note: It is important to measure output voltage before connecting devices. This helps avoid potential damage.
4. When the use of stand-by batteries are desired, they must be lead acid or gel type.
Connect batter
y to terminals marked [--- BAT +] (battery leads included).
Note: When batteries are not used a loss of AC will result in the loss of output voltage.
5. Connect appropriate signaling notification devices to A
C Fail & Low battery supervisory
relay outputs marked [NC, C, NO].
LED Diagnostics:
Terminal Identification:
OLS350, OLS350220
Offline Switching Power Supply/Charger
24VDC output.
Input: OLS350 - 115V
AC / 60Hz 5.0 amp or
OLS350220 - 220V
AC / 50Hz 3.0 amp.
Maximum charge current 0.7 amp.
12 amp continuous supply current at 24VDC.
Filtered and electronically regulated outputs.
Built-in charger for sealed lead acid or gel type batteries.
Automatic switch over to stand-by battery when
AC fails (zero voltage drop).
AC input and DC output LED indicators.
AC fail supervision (form "C" contacts).
Low battery supervision (form "C" contacts).
Short circuit overload protection.
Includes battery leads.
Board Dimensions: 4.5”W x 7.5”L x 1.75”H
Specified at 25˚ C ambient.
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC, Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Legend Power Supply Status
L, G, N Connect 115VAC to these terminals: L to Hot, N to Neutral, G to ground.
--- D C + 24VDC @ 12 amp continuous output.
AC FAIL
NC, C, NO
Used to notify loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present. Contact rating 1 amp @ 28VDC
Low Battery
NC, C, NO
Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized
when DC power is present.
Contact rating 1 amp @ 28VDC.
Low battery threshold: 24VDC output threshold set @ approximately 20.5VDC.
--- BAT + Stand-by battery connections. Maximum charge rate 0.7 amp.