Overview
The AL600ULACMCB converts a 115VAC 60Hz input into eight (8) independently
controlled 12VDC or 24VDC Fail-Safe and/or Fail-Secure outputs with a total of 6 amp
continuous supply current. Outputs are activated by an open collector sink or normally
open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push
Button, PIR, etc. This unit will route power to a variety of access control hardware devices
including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. The outputs will
operate in both Fail-Safe and/or Fail-Secure modes. This unit is designed to be powered
by one common power source (factory installed) which will provide power for both the
board operation and locking devices, or two (2) totally independent power sources, one (1)
providing power for board operation and the other for lock / accessory power. The FACP
Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other
auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all
of the eight (8) outputs.
AL600ULACMCB
Power Supply/Chargers w/Multi-Output
Access Power Controllers
Rev. DSAL600ULACMCB_01032013
Specifications
Input:
• Input115VAC60Hzrated@3.5amp.
• Powersupplyinputoptions:
a) One (1) common power input for ACM8CB and
lock power (factory installed).
b) Two (2) isolated power inputs - One (1) to power
the ACM8CB and one (1) for lock accessory power,
(external power supply is required). (Current is
determined by the power supply connected, not to
exceed a maximum of 10 amp total).
• Eight(8)AccessControlSystemtriggerinputs.
Inputoptions:
a) Eight (8) normally open (NO) inputs.
b) Eight (8) open collector inputs.
c) Any combination of the above.
Output:
• 12VDCor24VDC@6ampsupplycurrent.
• Class2Ratedpowerlimitedoutputs.
• Eight(8)independentlycontrolledoutputs.
Outputoptions:
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs.
b) Eight (8) form “C” 5 amp rated relay outputs
c) Any combination of the above.
• Eight(8)auxiliarypoweroutputs(unswitched)
• Outputratings:
-PTCsarerated@2.5amp.
• Filteredandelectronicallyregulatedoutputs
(built-in power supply).
Features:
• FireAlarmdisconnect(latchingornon-latching)is
individually selectable for any or all of the
eight (8) outputs.
• FireAlarmdisconnectinputoptions:
a) Normally open (NO) or normally closed (NC)
dry contact input.
b) Polarity reversal input from FACP signaling circuit.
Features (cont’d):
• AlarmoutputrelayindicatesthatFACPinputis
triggered(form“C”contactrated@1amp28VDC).
• Shortcircuitandthermaloverloadprotection.
• ACfailsupervision(form“C”contact).
Visual Indicators:
• RedLEDsindicateoutputsaretriggered
(relays energized).
• GreenLEDindicatesFACPdisconnectistriggered.
• ACinputandDCoutputLEDindicators.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• AL600ULXB(PowerSupplyBoard)maximum
charge current 0.7 amp.
• Automaticswitchovertostand-bybatterywhenACfails.
• Zerovoltagedropwhenunitswitchesovertobattery
backup (AC failure condition).
• Batteryfailandbatterypresencesupervision
(form “C” contact).
Electrical:
• Operatingtemperature:0ºCto49ºCambient.
• ACM8CBboardmainfuseisratedat10amp.
• BTU/Hr.:
- 12VDC:36.85BTU/Hr.
- 24VDC:73.70BTU/Hr.
Mechanical:
• EnclosureDimensions(LxWxHapprox.):
15.5”(393.7mm)x12”(304.8mm)x4.5”(114.3mm).
• Enclosureaccommodatesuptotwo(2)12AHbatteries.
• Productweight(approx.):10.3 lbs. (4.67 kg).
• Shippingweight(approx.):11.6lbs.(5.26kg).
AL600ULACMCB
Vue de la page 0
1 2

Résumé du contenu

Page 1 - AL600ULACMCB

OverviewThe AL600ULACMCB converts a 115VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC Fail-Safe and/or Fail-Secure outputs with

Page 2 - Agency Approvals

UL Listed for Access Control Systems Units (UL294).Agency ApprovalsMEA - NYC Department of Buildings Approved.Altronix Corp.140 58th St. Brooklyn

Commentaires sur ces manuels

Pas de commentaire