Altronix AL1024ULX Fiche technique

Naviguer en ligne ou télécharger Fiche technique pour Extensions de puissance Altronix AL1024ULX. Altronix AL1024ULX power extension Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 2
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Agency Approvals
Specifications
UL 294 UL Listed for Access Control
System Units.
UL 1481 UL Listed Standard for Safety for
Fire Protective Signaling Systems.
CUL Listed - CSA Standard C22.2
No.205-M1983, Signal Equipment.
MEA - NYC Department of
Buildings Approved.
CSFM - California State Fire
Marshal Approved.
FM - Factory Mutual Approved.
Input:
• Input115VAC/60Hz,4.4amp.
• Inputfuserated@3.5amp/250V.
Output:
• 24VDCoutput.
•10ampofcontinuoussupplycurrentfor
Access Control applications.
• 8ampofcontinuoussupplycurrentfor
Fire Alarm applications.
• Filteredandelectronicallyregulatedoutput.
• Shortcircuitandthermaloverloadprotection.
Battery Backup:
• Built-inchargerforsealedleadacidor
gel type batteries.
• Automaticswitchovertostand-bybattery
whenACfails.
• Maximumchargecurrent3.6amp.
Supervision:
• ACfailsupervision(form“C”contacts).
• Lowbatterysupervision(form“C”contacts).
• Batterypresencesupervision(form“C”contacts).
Visual Indicators:
• ACinputandDCoutputLEDindicators.
Electrical:
• Operatingtemperature:0ºCto49ºCambient.
• 45-91BTU/Hr.:
• SystemACinputVArequirement:506VA.
Mechanical:
• EnclosureDimensions(HxWxDapprox.):
15.5”(393.7mm)x12”(304.8mm)x4.5”(114.3mm)
- Accommodatesuptotwo(2)12VDC/12AHbatteries.
• Productweight(approx.):10.1lbs.(4.58kg.).
• Shippingweight(approx.):11.4lbs.(5.17kg.).
AL1024ULXisamulti-agencyapprovedsingleoutputpowersupply/chargerwhich
convertsa115VAC/60Hzinputintoone(1)24VDCnon-powerlimitedoutput.
AL1024ULX
Power Supply/Charger
Rev.DSAL1024ULX_01062012
Overview
AL1024ULX
Vue de la page 0
1 2

Résumé du contenu

Page 1 - Power Supply/Charger

Agency ApprovalsSpecificationsUL 294 UL Listed for Access Control System Units.UL 1481 UL Listed Standard for Safety for Fire Protective Signali

Page 2 - (H x W x D) (approximate):

1.5”(38.1mm)1.5”(38.1mm)1.5”(38.1mm)5.0”(127.0mm)5.0”(127.0mm)1.5”(38.1mm)2.0”(50.8mm)2.0”(50.8mm)1.75”(44.45mm)1.75”(44.45mm)4.5”(114.3mm)1.25”(31.75

Commentaires sur ces manuels

Pas de commentaire