NAC Power ExtenderInstallation GuideFireSwitch108- 10 amp NAC Power ExtenderRev. 090414 More than just power.™TM
- 10 - FireSwitch108Trouble Memory LCD Indication:LCD Legend Trouble ConditionA AC trouble.B Battery trouble.C Common trouble.N Normal operating co
FireSwitch108 - 11 -Battery Calculation Worksheet:DeviceNumber of DevicesCurrent per DeviceStand-by CurrentAlarm CurrentForeachdeviceuse
- 12 - FireSwitch108FireSwitch Applications:1. General Information: Altronix FireSwitch units are very versatile devices. They can be used with o
FireSwitch108 - 13 -Horn settings for CO alarm:Gentex,Potter-HornsmustbesettoSteadymode.SystemSensor-Hornsmustbesetforacodedoutp
- 14 - FireSwitch1086. Synchronizing NAC Power Extender Using Built-in Sync Protocol: FireSwitch units include built-in protocols to support Amsec
FireSwitch108 - 15 - INP1 RET1 NEGATIVE POSITIVE + SYNC --- NC GND NC NO C EARTH INP2 RET2 NEGATIVE POSITIVE + SYNC --- NC GND NC NO
- 16 - FireSwitch1088. Using a Single FACP Output: When only one FACP output is available, you may connect both Input1 and Input2 to it. Wire [RET
FireSwitch108 - 17 -Appendix A - UL/cUL Listed Compatible Devices for SynchronizationA-1 Strobes, Horns and Horn/StrobesTableA-1belowlistsStro
- 18 - FireSwitch108Appendix A - UL/cUL Listed Compatible Devices for Synchronization (cont’d)A-1 Strobes, Horns and Horn/StrobesTableA-1belowl
FireSwitch108 - 19 -Appendix A - UL/cUL Listed Compatible Devices for Synchronization (cont’d)A-1 Strobes, Horns and Horn/StrobesTableA-1belowl
- 2 - FireSwitch108Overview:The Altronix FireSwitch108 is a cost effective managed NAC Power Extender. It interfaces with 12 or 24VDC Fire Alarm C
- 20 - FireSwitch108Altronix is not responsible for any typographical errors.14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-
FireSwitch108 - 3 -lineneutralground L NFig. 1Power Supply Specifications:AC Input120VAC60Hz,4.8amp.OutputEight (8) regulated supervised NAC o
- 4 - FireSwitch108 enclosureULListedforappropriateapplication.Separatebatteryenclosureisrequiredtohave50cubicinchesof additiona
FireSwitch108 - 5 - ForClassBoutputsconnectEOL(AL-EOL10)tothelastdeviceineachNACLoop.ForapplicationsinCanada useEOL10K-Cend
- 6 - FireSwitch108OPEN SWITCH CLOSED SWITCH Switch Detail Fig. 3Terminal Identification Table:Power Supply BoardTerminal Legend Function/Descript
FireSwitch108 - 7 -CommonTrouble SyncPower-LimitedEthernetConnectionRegulatedSupervisedNAC OutputsPower-LimitedRegulatedNAC OutputsPower-LimitedAux
- 8 - FireSwitch108Connection Diagram:Fig. 5Programming:To begin programming depress and hold down the joystick (approximately 2 secs.). Note: If
FireSwitch108 - 9 -Protocol Selection:LCDLegendFunction Triggered From Description1aSteadyInput 1A steady output signal will be generated. This mod